MIQ Thermon Dây Gia Nhiệt Dùng Cho Dầu Khí
MIQ high performance mineral insulated heating cables are used extensively for high temperature maintenance, high temperature exposure and/or high watt density applications which exceed the limitations of thermoplastic insulated cables. The resistance configurations available can provide tracing for pipes up to 1.6 km (1 mile) long from a single power supply point.
Thermon’s MIQ mineral insulated cables are manufactured using Alloy 825, a high nickel/chromium alloy ideally suited for high temperature service that offers exceptional resistance to stress corrosion in chloride, acid, salt and alkaline environments.
APPLICATION
MIQ high performance mineral insulated heating cables are
used extensively for high temperature maintenance, high
temperature exposure and/or high watt density applications
which exceed the limitations of thermoplastic insulated
cables. The resistance configurations available can provide
tracing for pipes up to 1 mile (1.6 km) long from a single
power supply point.
Thermon’s MIQ mineral insulated cables are manufactured
using Alloy 825, a high nickel/chromium alloy ideally
suited for high temperature service that offers exceptional
resistance to stress corrosion in chloride, acid, salt and
alkaline environments.
MIQ cables are approved for use in ordinary (nonclassified)
areas and hazardous (classified) areas.
RATINGS
Rated voltage 1 ......................................300 and 600 Vac
Max. maintenance temperature 2 ..............932°F (500°C)
Max. continuous exposure temperature
Power-off............................................1,112°F (600°C)
Max. watt density 2....................... up to 80 w/ft (262 w/m)
Minimum installation temperature............... -76°F (-60°C)
Minimum bend radius ................................ 6 x cable O.D.
PRODUCT SPECIFICATIONS
MIQ™ MINERAL INSULATED CABLE
1
2
3
D
Pigtail
Cold Lead
Two Conductor Heated Length
Hot-End Termination
Used With 300 or 600 Vac, Two Conductor Cable
B
Pigtail
Cold Lead
One Conductor Heated Length
Used With 600 Vac, One Conductor Cable
Heater Set Types
E Pigtail
Cold Lead
Two Conductor Heated Length
Pigtail
Cold Lead
Used With 300 or 600 Vac, Two Conductor Cable
A Pigtail
Cold Lead
One Conductor Heated Length
Used With 600 Vac, One Conductor Cable
D / MIQ-50E3H-2S / 200 / 1404 / 120 / 4 / 12 / 6 / 1
Design (A,B,D,E)
Cable Reference
Length (metric lengths followed by "M")
Watts
Volts
Cold Lead Length (metric lengths followed by "M")
Cold Lead size (AWG)
Cold Lead Voltage Rating
Hazardous (Classified) Location Rating 4
MIQ CATALOG REFERENCE NUMBER
A complete catalogue reference number includes the
following components:
THERMON The Heat Tracing Specialists®
Corporate Headquarters:100 Thermon Dr • PO Box 609 San Marcos, TX 78667-0609 • Phone: 512-396-5801 • 1-800-820-4328
For the Thermon office nearest you visit us at . . . www.thermon.com
Form TEP0020-0714 • © Thermon Manufacturing Co. • Printed in U.S.A. • Information subject to change.
Notes
1. Definition as stated in IEEE Standard 515. Specific voltage depends on circuit
length and design conditions.
2. Watt density limitations are correlated to maintain temperatures.
3. Contact Thermon for gland size information.
4. If the field is blank, then the heating cable set is intended for ordinary (nonclassified) locations or Division 2 locations, or for use with AEx de, or Ex e
enclosures. If the value in the field is “1”, then the heating cable set is intended
for Division 1 locations, or for use with AEx d, or Ex d enclosures.
CONSTRUCTION
1 Solid alloy or copper conductor(s)
2 Compacted magnesium oxide insulation
3 Seamless alloy 825 sheath
MIQ HEATER SETS
Thermon MIQ cable sets are available in four factory
fabricated configurations: Type A, B, D or E. The standard
assemblies consist of a predetermined length of heating
cable joined to a standard 4’ (1.2 m) or 7’ (2.1 m) nonheating
cold lead with 12” (305 mm) long thermoplastic insulated
pigtails.
The nonheating section of the unit is sealed and fitted with
a high pressure, liquid-tight 1/2” or 3/4” NPT stainless steel
gland 3 for connection into the supply junction box.
CIRCUIT BREAKER SIZING 2
Maximum circuit lengths for various circuit breaker
amperages are shown. Breaker sizing should be based
on the National Electrical Code, Canadian Electrical Code
or any other applicable code. The National Electrical
Code and Canadian Electrical Code require ground-fault
protection of equipment for each branch circuit supplying
electric heating equipment. Che